SF-104B digital temperature controller
Features
Temperature Display/ Temperature Control
Manual, automatic defrost by electric heater
Evap. Fan Control
Time、temp setting to end defrost
Value Storing/ Self Testing
Parameter Locking
Technical Data
Range of temperature displayed : —45~66℃ (-45~150℉)
Range of set temperature: —45~45℃ (-45~120℉)
Accuracy:±1℃ (±2℉)
Compressor: N.O. 30A/250VAC
Defrost: N.O. 10A/250VAC
Evap.Fan: N.O. 5A/250VAC
Dimension:77(Length)×35(Width)×70(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
Parameters
Parameter |
Function |
Set range |
Default |
E1 |
Lower setpoint limit |
-45℃/-45℉~Set temp. |
-22℃/-8℉ |
E2 |
Higher setpoint limit |
Set temp.~45℃/120℉ |
20℃/68℉ |
E3 |
Temp.Hysteresis |
1~10℃/1~18℉ |
4℃/7℉ |
E4 |
Comp.start delay time |
0~10Min |
03Min |
E5 |
Offset on room temp. |
-20~20℃/-20~20℉ |
0 |
E6 |
Offset on evap.temp. |
-20~20℃/-20~20℉ |
0 |
C1 |
Temperature unit |
℃=Celsius ℉=Fahrenheit |
℃ |
F1 |
Max.defrost duration |
1~60Min |
20Min |
F2 |
Defrost interval time |
0~24Hr |
04Hr |
F3 |
Defrost termination temp. |
0~20℃/32~68℉ |
8℃/46℉ |
F4 |
Display during defrost |
0=Normal display |
0 |
F5 |
Fan operating function |
0=Parallel with comp. 1=Continuous running except defrost |
0 |