Features
Temperature Display/ Temperature Control
Manual, automatic defrost/Time setting to end defrost
Highest and lowest temperature memorization
Alarm delay/Door switch/Value storing
Parameter locking/Self testing
Technical Data
Range of temperature displayed:-45~66.0℃
Range of set temperature:-19.9~20.0℃
Accuracy:±1℃
Temperature sensor: NTC, Double sensors (for cold room&product temperature control),2m(L)
Compressor:N.O..30A/250VAC (can directly connect 1HP compressor, if more needs to connect an AC contactor)
Light : N.O.5A/250VAC
Alarm:N.O.5A/250VAC
Dimension:77(Length)×35(Width)×70(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
Parameters
Parameter |
Function |
Set range |
Default |
PAS |
Password |
00~99 |
15 |
E1 |
Lower setpoint limit |
-19.9℃~Set temp. |
2.0℃ |
E2 |
Higher setpoint limit |
Set temp.~2.0℃ |
10.0℃ |
E3 |
Temp. Hysteresis |
0.1~20.0℃ |
0.4℃ |
E40 |
Turning on delay time |
0~10Min |
3Min |
E41 |
Comp. Start delay time |
0~10Min |
3Min |
E5 |
Offset on room temp. |
-19.9~20.0℃ |
0℃/0℉ |
E6 |
Offset on evap. Temp. |
-19.9~20.0℃ |
0℃/0℉ |
F0 |
Defrost type |
00=defrost by turning off comp. |
00 |
F1 |
Max defrost duration. |
01~60Min |
1Min |
F2 |
Defrost interval time. |
00~24Hr |
00 |
F4 |
Display during defrost. |
00=clod room temp. Display normally 01=last value before defrost 02=fixed display cold room temp 03=display DEF |
00 |
C1 |
Cold room high temp. Alarm |
C2~20.0℃ |
10.0℃ |
C2 |
Cold room low temp. Alarm |
-19.9℃~C1 |
2.0℃ |
C3 |
Product temp.high temp. Alarm |
-19.9~20.0℃ |
20.0℃ |
-