搜索
1/1
Number of views:
0
1
Description
Features
Temperature Control
The alarm function
The alarm single output
Refrigerating & heating modes selection
Celsiuc/Fahrenheit degrees
Value Storing / Self Testing
Technical Data
Range of temperature display:-45~120℃ (-40~248℉)
Range of set temperature:-45~120℃ (-40~248℉)
Accuracy:±1.0℃ (±1.8℉)
Resolution:0.1℃(-19.9~99.9℃)
Control output: N.O. 16A/250VAC
Alarm output: N.O. 5A/250VAC
Dimension:77(Length)×35(Width)×60(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
Parameters
Paramete
|
Function
|
Set range
|
Default
|
E1
|
Lower setpoint limit
|
-45℃/-49℉~Set temp.
|
-35℃/-31℉
|
E2
|
Higher setpoint limit
|
Set temp.~120℃/248℉
|
90℃/194℉
|
E3
|
Temp.hysteresis
|
0.1~30.0℃/0.2~54.0℉
|
4.0℃/7.2℉
|
E4
|
Comp.start delay time
|
0~10Min
|
2Min
|
E5
|
Offset on room temp.
|
-19.9~20.0℃/-35.0~36.0℉
|
0
|
C1
|
Temperature unit
|
0=℃?? 1=℉
|
0
|
C2
|
Temperature control mode
|
0=refrigerating?? 1=heating
|
0
|
P1
|
High temperature alarm value
|
-45~100℃/-49~212℉
|
45℃/113℉
|
P2
|
Low temperature alarm value
|
-45~100℃/-49~212℉
|
-40℃/-40℉
|
P3
|
Alarm delay time
|
0~90Min
|
60Min
|
P4
|
Alarm hysteresis
|
0.1~10.0℃/0.2~18.0℉
|
2.0℃/3.6℉
|
Previous
None
Next
None
-
Mandy Lam
Lynn Mai -
Kay
Carmen Chan - Tel (0086)760-88787946
- TOP