Features
Temperature display
Refrigeration control
Defrost by turning off
Cold-room、Condenser high temperature alarm
Defog Control / Password control
Parameter locking / Set testing
Technical Data
Range of temperature displayed : -45~120℃(-45~248℉)
Control temperature step value:1℃/1℉
Range of set temperature: -40~120℃(-40~248℉)
Temperature sensor:NTC, one sensor,2m(L)
Compressor: N.O. 30A/250VAC
Defog: N.O. 8A/250VAC
Dimension:181(Length)×41(Width)×68(Depth)mm
Mounting hole dimension:138(Length)×32.5(Width)mm
Parameters
Paramete |
Function |
Set range |
Default |
E1 |
Lower setpoint limit |
-40℃/-40℉~Set temp. |
-25℃/-13℉ |
E2 |
Higher setpoint limit |
Set temp.~120℃/248℉ |
60℃/140℉ |
E3 |
Temp.hysteresis |
1~10℃/2~18℉ |
2℃/4℉ |
E4 |
Comp.start delay time |
0~10Min |
3Min |
E5 |
Offset on room temp. |
-10~10℃/-18~18℉ |
0 |
F1 |
Max.Defrost duration |
1~60Min |
20Min |
F2 |
Defrost interval time |
0~24Hr |
0Hr |
F4 |
Display during defrost |
0=Normal display 1 = Last value before defrost 2=Display "DFE " |
0 |
-