Features 

It is an intelligent controller and applicable to the compressor of one HP.

Temperature Di splay/Temperature Control

Automatic defrost by electric heater or hot gas

Door switch inspection alarm

High,Low temperature alarm

Condenser high temperature alarm

/Self Testing /Parameter Locking

Memory setting


Technical Data 
Range of temperature display:-45~150℃       

Range of set temperature:-45~50℃         

Accuracy:±1℃

Temperature sensor: NTC, 3 sensors,2m(L) (cold room,defrost control,condensor high temperature alarm)

Compressor: N.O. 30A/250VAC

(appl icable to one HPCompressor,if more it needs to connect anAC contactor)

Defrost: N.O. 30A/250VAC

Evap. Fan: N.O. 30A/250VAC

Panel dimensions:142(Length) 38(Width) 35(Depth)mm

Mounting hole dimensions:137(Length) 31.5(Width)mm

Parameters 

 

Paramete

Function

Set range

Default

E1

Lower setpoint limit

-45℃~Set temp.

-30℃

E2

Higher setpoint limit

Set temp.~50℃

30℃

E3

Temp.hysteresis

1~10℃

4℃

E4

Comp.start delay time

0~10Min

2Min

E5

Offset on room temp.

-10~10℃

0

E6

Offset on evap.temp.

-10~10℃

0

F0

Defrost function

0=Electric heater

1=Hot gas

0

F1

Max.Defrost duration

1~60Min

20Min

F2

Defrost interval time

0~24Hr

6Hr

F3

Defrost termination temp.

0~50~0℃

8℃

F4

Display during defrost

0=Normal display
1=Last value before defrost

0

F5

Dripping time after defrost

0~10Min

2Min

H1

Fan start delay time

0~10Min

 

We could not find any corresponding parameters, please add them to the properties table
Previous
Next

Attachment Download

  • SF-205N1

    Categories:

    Products

    File size:

    74KB

    Time:

    2020-11-03 09:22:13

    Dependent population:

    All

SF-205N1
Categories:
Products
File size:
74KB
2020-11-03 09:22:13
Dependent population:
All
Page up
1