Features 
Temperature Control / Evap. Fan Control
Manual, automatic defrost by electric heater / hot gas
Time、temperature setting to end defrosting
High、low temperature alarm
Condenser high temperature alarm
Value Storing / Self Testing 

Technical Data 
Range of temperature displayed : —45~150℃ (-45~302℉)
Range of set temperature: —45~100℃ (-45~212℉)  
Accuracy:±1℃ (±2℉)
Compressor: N.O. 30A/250VAC
Defrost: N.O. 10A/250VAC
Evap.Fan: N.O. 5A/250VAC
Dimension:77(Length)×35(Width)×70(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm 

Parameters 
 

Paramete
Function
Set range
Default
E1
Lower setpoint limit
-45℃/-45℉~Set temp.
-35℃/-31℉
E2
Higher setpoint limit
Set temp.~100℃/212℉
20℃/68℉
E3
Temp.hysteresis
1~20℃/1~36℉
4℃/7℉
E4
Comp.start delay time
0~10Min
2Min
E5
Offset on room temp.
-20~20℃/-36~36℉
0
E6
Offset on evap.temp.
-20~20℃/-36~36℉
0
E7
Offset on condens
-20~20℃/-36~36℉
0
F0
Defrost function
0=Electric heater 
1=Hot gas
0
F1
Max.Defrost duration
1~60Min
20Min
F2
Defrost interval time
0~24Hr
4Hr
F3
Defrost termination temp.
0~30℃/32~86℉
8℃/46℉
F4
Display during defrost
0=Normal display
1=Last value before defrost
0
F5
Fan operating function
0=Parallel with comp.
1=Continuous running except defrost
0
C1
Temperature unit
℃=Celsius   ℉=Fahr.
C2
High temperature alarm
C3~100℃/212℉
40℃/104℉
C3
Low temperature alarm
-45℃/-45℉~C2
-40℃/-40℉
C4
Alarm delay time
1~90Min
60Min
C5
Condenser high temperature alarm value
0~120℃/0~248℉
80℃/176℉
We could not find any corresponding parameters, please add them to the properties table

Attachment Download

  • SF-108

    Categories:

    Products

    File size:

    157KB

    Time:

    2020-11-03 09:25:02

    Dependent population:

    All

SF-108
Categories:
Products
File size:
157KB
2020-11-03 09:25:02
Dependent population:
All
Page up
1