  • 5(1705980741251).jpg
  • 86dc6be996b48f39cb4fd7f1ecdd9a43_9c813e5c-6182-47c3-8d70-9325ec29c114._1180xaf.jpg
  • 2b3b8f08b146d9702f86eb40d811ea57_f44bfc45-fcda-45cc-a977-3ebede647c1f._1180xaf.jpg
  • 28edc8c3465105f2dfedac8e26c0b14e_e6dec46e-f428-472d-94b6-c0a00ef32165._270xaf.jpg
  • 8d5fea2c5673b38346987a27122c457b_722cd8de-d996-423f-81ba-ae922d5cf88c._640xaf.jpg
  • 45ec51112fc62246111b7c27559f3ec2_7b3f5819-8932-4301-a24a-cf44eeab0595._640xaf.jpg

SF-108 digital temperature controller


Product number:1033013071057870848

  • Description
  • Features 
    Temperature Control / Evap. Fan Control
    Manual, automatic defrost by electric heater / hot gas
    Time、temperature setting to end defrosting
    High、low temperature alarm
    Condenser high temperature alarm
    Value Storing / Self Testing 

    Technical Data 
    Range of temperature displayed : —45~150℃ (-45~302℉)
    Range of set temperature: —45~100℃ (-45~212℉)  
    Accuracy:±1℃ (±2℉)
    Compressor: N.O. 30A/250VAC
    Defrost: N.O. 10A/250VAC
    Evap.Fan: N.O. 5A/250VAC
    Dimension:77(Length)×35(Width)×70(Depth)mm
    Mounting hole dimension:71(Length)×29(Width)mm 

    Parameters 
     

    Paramete
    Function
    Set range
    Default
    E1
    Lower setpoint limit
    -45℃/-45℉~Set temp.
    -35℃/-31℉
    E2
    Higher setpoint limit
    Set temp.~100℃/212℉
    20℃/68℉
    E3
    Temp.hysteresis
    1~20℃/1~36℉
    4℃/7℉
    E4
    Comp.start delay time
    0~10Min
    2Min
    E5
    Offset on room temp.
    -20~20℃/-36~36℉
    0
    E6
    Offset on evap.temp.
    -20~20℃/-36~36℉
    0
    E7
    Offset on condens
    -20~20℃/-36~36℉
    0
    F0
    Defrost function
    0=Electric heater 
    1=Hot gas
    0
    F1
    Max.Defrost duration
    1~60Min
    20Min
    F2
    Defrost interval time
    0~24Hr
    4Hr
    F3
    Defrost termination temp.
    0~30℃/32~86℉
    8℃/46℉
    F4
    Display during defrost
    0=Normal display
    1=Last value before defrost
    0
    F5
    Fan operating function
    0=Parallel with comp.
    1=Continuous running except defrost
    0
    C1
    Temperature unit
    ℃=Celsius   ℉=Fahr.
    C2
    High temperature alarm
    C3~100℃/212℉
    40℃/104℉
    C3
    Low temperature alarm
    -45℃/-45℉~C2
    -40℃/-40℉
    C4
    Alarm delay time
    1~90Min
    60Min
    C5
    Condenser high temperature alarm value
    0~120℃/0~248℉
    80℃/176℉

Products Message