Description
Features
Temperature Control / Evap.Fan Control
Manual/automatic defrost by electric heater,hot gas
Time/temp.setting to end defrost
High,Low temperature alarm
Re-start delay / Parameters locking
Technical Data
Range of temperature displayed : —45~150℃ (-45~150℉)
Range of set temperature: —45~45℃ (-45~113℉)
Accuracy:±1.0℃ (±1.8℉)
Resoluition:0.1℃(-19.9~99.9℃)
Compressor: N.O. 16A/250VAC
Defrost: N.O. 10A/250VAC
Evap.Fan: N.O. 5A/250VAC
Dimension:77(Length)×35(Width)×60(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
Parameters
Paramete
|
Function
|
Set range
|
Default
|
E1
|
Lower setpoint limit
|
-45℃/-45℉~Set temp.
|
-31℃/-35℉
|
E2
|
Higher setpoint limit
|
Set temp.~45℃/113℉
|
45℃/113℉
|
E3
|
Temp.hysteresis
|
1~20.0℃/1.8~36.0℉
|
4.0℃/7.2℉
|
E4
|
Comp.start delay time
|
0~10Min
|
2Min
|
E5
|
Offset on room temp.
|
-20.0~20.0℃/-36.0~36.0℉
|
0
|
E6
|
Offset on evap.temp.
|
-20.0~20.0℃/-36.0~36.0℉
|
0
|
F0
|
Defrost function
|
0=Electric heater
1=Hot gas
|
0
|
F1
|
Max.Defrost duration
|
1~60Min
|
20Min
|
F2
|
Defrost interval time
|
0~24Hr
|
6Hr
|
F3
|
Defrost termination temp.
|
0~30℃/32~68℉
|
8℃/46℉
|
F4
|
Display during defrost
|
0=Normal display
1=Last value before defrost |
0
|
F5
|
Dripping time
|
0~30Min
|
2Min
|
F6
|
Temperature display delay time after defrosting(F4=1)
|
0~60Min
|
20Min
|
H1
|
Fan start delay time after defrosting
|
0~10Min
|
1Min
|
H2
|
Fan operating function
|
0=Parallel with comp.,close when defrosting
1=Continuous running except defrosting
2=Parallel with comp.,open when defrosting
3=Continuous running except defrosting
4=Start temperature(rests with evap.temp.
5=Start temperature (rests with the temperature in cold-room)
|
4
|
H3
|
Fan start temp.(H2=4,5)
|
-30~30℃/-22~86℉
|
5℃/41℉
|
H4
|
Fan delay after time after comopressor stops.(H2=1,2H)
|
0~30Min
|
0Min
|
C0
|
Resolutio
|
0.1/1?℃/℉
|
0.1
|
C1
|
Temperature unit
|
0=Celsius?? 1=Fahrenheit
|
C
|
C2
|
High temperature alarm
|
C3~130℃/ C3~130℉
|
50℃/122℉
|
C3
|
Low temperature alarm
|
-40℃~C2/-40℉~C2
|
-40℃/-40℉
|
C4
|
Alarm delay time
|
1~90Min
|
60Min
|