Features
It is a mini-sized and integrated intelligent controller
Temperature Control / Manual,automatic defrost
Evap.Fan Control / Defrost by electric heater、hot gas
Time/temp.Setting to end defrost / Value Storing / Self Testing
Technical Data
Range of temperature displayed:-45~150℃ (-45~302℉)
Range of set temperature:-45~45℃ (-45~113℉)
Accuracy:±1.0℃(±1.8℉)
Temperature sensor: NTC, double sensors (for cold-room temp. & defrost control), 2m(L)
Compressor: N.O. 16A/250VAC
Defrost: N.O. 10A/250VAC
Evap.Fan: N.O. 5A/250VAC
Dimension:77(Length)×35(Width)×60(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
Parameters
Paramete |
Function |
Set range |
Default |
E1 |
Lower setpoint limit |
-45℉/-45℃~Set temp. |
-31℉/-35℃ |
E2 |
Higher setpoint limit |
Set temp.~113℉/45℃ |
113℉/45℃ |
E3 |
Temp.hysteresis |
0.2~36.0℉/0.1~20.0℃ |
7.2℉/4.0℃ |
E4 |
Comp.start delay time |
0~10Min |
2Min |
E5 |
Offset on room temp. |
-36.0~36.0℉/-20.0~20.0℃ |
0 |
E6 |
Offset on evap. temp |
-36.0~36.0℉/-20.0~20.0℃ |
0 |
F0 |
Defrost function |
0=Electric heater 1=Hot gas |
0 |
F1 |
Max. Defrost duration |
1~60Min |
20Min |
F2 |
Defrost interval time |
0~24Hr |
6Hr |
F3 |
Defrost termination temp. |
32~86℉/0~30℃ |
46℉/8℃ |
F4 |
Display during defrost |
0=Nomal display 1 = Last value before defrost |
0 |
F5 |
Fan operating function |
0=Parallel with comp. 1 = Continuous running except defrost |
0 |
F6 |
Dripping time |
0~30Min |
2 |
F7 |
Fan operating function after defrost end |
0=Temperature 1=Time |
1 |
F8 |
Fan start -up delay after defrost end |
0~10Min |
2 |
F9 |
Fan start temperature after defrosting(evaporator) |
-22~86℉ -30~30℃ |
41℉ 5℃ |
-