Features
Refrigeration control
Hot gas、heating defrost function
Cold room sensor high, low temperature alarm
Evap. Fan Control / Password control
Defog control / Value Storing
Technical Data
Range of temperature displayed : -45~120℃(-49~248℉)
Control temperature step value:1℃/1℉
Range of set temperature : -40~120℃(-40~248℉)
Accuracy:±1%
Temperature sensor:NTC,Two sensors,2m(L
Refrigeration: 30A/250VAC
Defrost: 10A/250VAC
Evap. Fan: 8A/250VAC
Defog: 8A/250VAC
Dimension:181(Length)×41(Width)×68(Depth)mm
Mounting hole dimension:138(Length)×32.5(Width)mm
Parameters
Paramete |
Function |
Set range |
Default |
E1 |
Lower setpoint limit |
-40℃/-40℉~Set temp. |
-25℃/-13℉ |
E2 |
Higher setpoint limit |
Set temp.~120℃/248℉ |
60℃/140℉ |
E3 |
Temp.hysteresis |
1~10℃/2~18℉ |
2℃/4℉ |
E4 |
Comp.start delay time |
0~10Min |
3Min |
E5 |
Offset on room temp. |
-10~10℃/-18~18℉ |
0 |
E6 |
Offset on evap.temp. |
-10~10℃/-18~18℉ |
0 |
F0 |
Defrost function |
0=Electric heater 1=Hot gas |
0 |
F1 |
Max.Defrost duration |
1~60Min |
20Min |
-