Features
Mini-sized and integrated temperature control
can directly control 1HP compressor (include 1HP)
Temperature display/Temperature control
Manual, automatic defrost
Evap. fan control
Energy saving mode/Light control
Value storing/Parameter locking/Self testing
Technical Data
Temperature display range:-45~66℃(-45~150℉)
Set temperature range:-40℃~45℃(-40~113℉)
Accuracy:±01℃(02℉)
Temperature sensor: NTC, two sensors (cold room&defrost control), 2 meters/
One door control switch line(optional)
Compressor N.O. 30A/250VAC(can directly connect to 1HP compressor, if more needs to connect anAC contactor)
Evap. Fan N.O. 5A/250VAC
Light:N.O 5A/250VAC
Increase dor (condenser sensor, door switch, alarm input) model selection input, when door control
input there is energy saving mode.
Dimension:77(L)mm×35(W)mm×70(D)mm
Mounting hole dimension: 71mm( L)×29mm(W)
Parameters
Paramete |
Function |
Set range |
Default |
PAS |
Password |
00~99 |
1 5 |
E1 |
Lowest set point limit |
-40℃/-40℉~Set temp. |
-25℃/-13℉ |
E2 |
Higher set point limit |
Set temp.~45℃/113℉ |
20℃/68℉ |
E3 |
hysteresis |
01~20℃/02~36℉ |
04℃/07℉ |
E40 |
Comp.start delay time |
0 0~1 0 Min |
2 Min |
E41 |
Delay starting time |
0 0~1 0 Min |
2 Min |
E5 |
Offset on room temp. |
-20~20℃/-36~36℉ |
00℃/00℉ |
E6 |
Offset on evap. Temp |
-20~20℃/-36~36℉ |
00℃/00℉ |
E7 |
Offset on condenser temp. |
-20~20℃/-36~36℉ |
00℃/00℉ |
-
Mandy Lam
Lynn Mai -
Kay
Carmen Chan - Tel (0086)760-88787946
- TOP