Features
Temperature control
Manual/automaticdefrost by electric heater
Evap. Fan Control
Value Storing
Self Testing /Parameter Locking
Technical Data
Range of temperature displayed : -45~150℃(-40~150℉)
Range of set temperature: -45~45℃(-40~120℉)
Accuracy:±1℃(±2℉)
Compressor: N.O. 30A/250VAC
Defrost: N.O. 10A/250VAC
Evap. Fan: N.O. 5A/250VAC
Dimension:77(Length)×35(Width)×70(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
Parameters
Parameter |
Function |
Set range |
Default |
PA |
Password |
00~99 |
|
E1 |
Lower setpoint limit |
-45℃/-45℉~Set temp. |
-22℃/-8℉ |
E2 |
Higher setpoint limit |
Set temp.~45℃/120℉ |
10℃/50℉ |
E3 |
Temp.Hysteresis |
1~20℃/1~36℉ |
5℃/9℉ |
E4 |
Comp.start delay time |
0~10Min |
2Min |
E5 |
Offset on room temp. |
-20~20℃/℉ |
0 |
E6 |
Offset on evap.temp. |
-20~20℃/℉ |
0 |
F1 |
Max.defrost duration |
1~60Min |
20Min |
F2 |
Defrost interval time |
0~24Hr |
4Hr |
F3 |
Defrost termination temp. |
0~30℃/32~68℉ |
12℃/54℉ |
F4 |
Display during defrost |
0=Normal display |
1 |
F5 |
Fan operating function |
0=Parallel with comp. 1 = Continuous running except defrost 2= Evaporator temper-ature control |
0 |
F6 |
Dripping time |
0~10 Min |
2Min |
F7 |
Fan delay start mode after defrost |
0=time 1=Controlled by F9 |
1 |
F8 |
Fan delay start time after defrost. |
0~10Min |
2
|
F9 |
Fan start temp. (Defrost sensor temp.) |
OFF~~44℃/44℉~Set value 0~90Min |
-