Features
Mini-sized and integrated temperature control
can directly control 1HP compressor (include 1HP)
Temperature display/Temperature control/Manual
automatically defrost
Evap. fan control
Time, temperature setting to end defrost
Energy saving mode
Value storing/ Parameter locking
Self testing
Technical Data
Temperature display range: -45~66℃(-45~150℉)
Set temperature range:-40℃~45℃(-40~113℉)
Accuracy:±01℃(02℉)
Temperature sensor: NTC, three sensors (cold room& defrost control), 2 meters (Neither positive nor negative) Condenser sensor, door switch (optional)
Compressor :N.O. 30A/250VAC (can directly connect to 1HP compressor, if more needs
to connect an AC contactor)
Defrost heater: N.O. 8A/250VAC (can directly connect to 1KWload, if more needs to
connect an AC contactor)
Evap. fan: N.O.5A/250VAC Alarm: N.O.5A/250VAC
Increase dor (condenser sensor, door switch, alarminput) model selection input, when
door control input there is energy saving mode.
Dimension:77(L)mm×35(W)mm×70(D)mm
Mounting hole dimension: 71mm( L)×29mm(W)
Parameters
Paramete |
Function |
Set range |
Default |
PAS |
Password |
0 0~99 |
1 5 |
E1 |
Lowest set point limit |
-40℃/-40℉~Set temp. |
-25℃/-13℉ |
E2 |
Higher set point limit |
Set temp.~45℃/113℉ |
20℃/68℉ |
E3 |
hysteresis |
01~20℃/02~36℉ |
04℃/07℉ |
E40 |
Comp.start delay time |
00~10Min |
2Min |
E41 |
Delay starting time |
00~10Min |
2Min |
E5 |
Offset on room temp. |
-20~20℃/-36~36℉ |
00℃/00℉ |
E6 |
Offset on evap. Temp |
-20~20℃/-36~36℉ |
00℃/00℉ |
E7 |
Offset on condenser temp. |
-20~20℃/-36~36℉ |
00℃/00℉ |
F0 |
Defrost type |
00=defrost by turning off comp. 01=heating defrost 02=hot gas defrost |
01 |
FF0 |
when enter hot gas defrost comp. delay starting time |
00~20Min |
00Min |
FF1 |
Defrost interval way |
00=power on time 01=comp. continuously working time |
00 |
-