Features
Temperature control
Evaporator fan control
Automatic/manual defrost
Defrost by electric heater
Time/temp. seting to end defrost
Re-start delay
Celsius/Fahrenheit degrees
Technical Data
Range of temperature display:-45~150℃ (-45~150℉)
Range of set temperature:-45~45℃ (-40~113℉)
Accuracy:±1℃(±2℉)
Compressor: N.O. 16A/250VAC
Defrost: N.O. 10A/250VAC
Evap. Fan: N.O. 5A/250VAC
Dimension:77(Length)×35(Width)×60(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
Parameters
Parameter |
Function |
Set range |
Default |
E1 |
Lower setpoint limit |
-45℃/-45℉~Set temp. |
-35℃/-31℉ |
E2 |
Higher setpoint limit |
Set temp.~45℃/113℉ |
45℃/113℉ |
E3 |
Temp.Hysteresis |
1~20℃/1.8~36℉ |
4.0℃/7.2℉ |
E4 |
Comp.start delay time |
0~10Min |
2Min |
E5 |
Offset on room temp. |
-20~20.0℃/-36.0~36.0℉ |
0 |
E6 |
Offset on evap.temp. |
-20~20.0℃/-36.0~36.0℉ |
0 |
F0 |
defrost function |
0=Electric heater 1=Hot gas |
0 |
F1 |
Max.defrost duration |
1~60Min |
20Min |
F2 |
Defrost interval time |
0~24Hr |
6Hr |
F3 |
Defrost termination temp. |
0~30℃/32~86℉ |
8℃/46℉ |
F4 |
Display during defrost |
0=Normal display |
0 |
F5 |
Fan operating function |
0=Parallel with comp. 1 = Continuous running except defrost |
0 |
F6 |
Dripping time |
0~30 Min |
2Min |
F7 |
Fan delay start mode after defrost |
0=temperature 1= time |
1 |
F8 |
Fan delay start time after defrosting. |
0~10Min |
2 Min |
F9 |
Fan start temperature after defrosting(evaporator) |
-30~30℃ -22~86℉ |
5℃ 41℉ |
C1 |
Temperature unit |
0s=℃ 1=℉ |
0 |
-