Features
Mini sized and integrated intelligent temperature control.
Temperature Display / Temperature Control /
Value Storing/Self Testing /Parameter Locking
Technical Data
Temperature sensor: NTC, one sensor, 2 meters long, neither positive nor negative
Range of temperature display:-45~120℃(-49~248℉)
Accuracy:±1℃ /±2℉
Range of set temperature:-45~45℃(-49~113℉)
Factory default : 04℃ /39℉
Dimension:150(Length)×93(Width)×45(Depth)mm
Mounting hole dimension:142.5(Length)×85.5(Width)mm
Relay output contact capacity
Compressor: N. O. 30A/250VAC
(applicable to one HP Compressor, if more it needs to connect an to AC contactor)
Evap. Fan: N. O. 10A/250VAC
Light: N. O. 10A/250VAC
Demist: N. O. 10A/250VAC
Paramete
Paramete | Function | Set range | Default |
E1 | Lower set point limit |
-49℉
-45℃~set temp.
|
-35℃
-31℉
|
E2 | Higher set point limit |
set temp.~113℉
45℃
|
20℃
68℉
|
E3 | Temp. hysteresis |
01~10℃
02~18℉
|
04℃
07℉
|
E4 | Comp. Start delay time | 00~10min | 2min |
E5 | Offset on room temp. |
-20~20℃
-36~36℉
|
00℃
00℉
|
F1 | Max. Defrost duration | 01~90 min | 20 min |
F2 | Defrost interval time | 00~24hr | 6hr |
F4 | Display during defrost |
00=Normal display
01 = Last value before defrost
02=display DEF
|
01 |
F5 | Fan control |
00=Parallel with comp.(stop when defrost)
01 = Continuous running
(stop when defrost)
02= Parallel with comp. (Start when defrost)
03=keep running(start when defrost)
|
03 |
C1 | High temp. alarm |
45℃
113℉ ~C2
|
45℃
113℉
|
C2 | Low temp. alarm |
-45℃
-49℉~C1
|
-40℃
-40℉
|
C3 | Alarm hysteresis |
01~20℃
02~36℉
|
02℃
04℉
|
C4 | Alarm delay time | 00~90min | 30min |
CF | Temp. unit | ℃=Celsius ℉=Fahrenheit | ℃ |
-