Mini-sized and integrated intelligent control .
Temperature Display / Temperature Control /
Value Storing /Parameter Locking/ Self Testing
Technical Data
Temperature sensor: NTC two sensors, 2m(L) (Neither positive nor negative)
Range of temperature displayed:-45℃~120℃(-49~248℉);
Accuracy:±1℃(±2℉)
Range of set temperature:-45℃~45℃(-49~113℉);
Factory default: 00℃(32℉)
Relay output contact capacity:
Compressor : N. O. 30A/250VAC
Fan: N. O. 10A/250VAC
Defrost: N. O. 10A/250VAC
Paramete
Paramete | Function | Set range | Default |
E1 | Lower set point limit |
-45℃
-49℉ ~set temp
|
-35℃
-31℉
|
E2 | Higher set point limit |
45℃
~set temp 113℉
|
20℃
68℉
|
E3 | Temp. Hysteresis |
01~10℃
02~18℉
|
04℃
07℉
|
E4 | Comp. start delay time | 00~10 min | 2 min |
E5 | Offset on room temp. |
-20~20℃
-36~36℉
|
00℃
00℉
|
E6 | Offset on evap. temp. |
-20~20℃
-36~36℉
|
00℃
00℉
|
F0 | Defrost type |
00=electric heat
01=hot gas
02=defrost by turning off
|
00 |
F1 | Defrost duration | 01~90min | 20 min |
F2 | Defrost interval | 00~24hr | 6 hr |
F3 |
Defrost termination
temp.
|
00~20℃
32~68℉
|
08℃
46℉
|
F4 |
Display
during defrost
|
00=normal display
01=last value before defrost
02=display dEF
|
01 |
F5 | Fan control |
00=synchonized with comp.(stop when defrost)
01=keep working(stop when defrost)
02=synchronized with comp.(start when defrost)
03=keep working(start when defrost)
|
01 |
F6 | Dripping time | 00~30min | 2 min |
C1 |
Cold room high
temp. Alarm
|
C2~ 45℃
113℉
|
45℃
113℉
|
C2 |
Cold room low
temp. Alarm
|
-45℃
-49℉ ~C1
|
-40℃
-40℉
|
C3 | Alarm hysteresis |
01~20℃
02~36℉
|
02℃
04℉
|
C4 | Alarm delay time | 00~90min | 30 min |
CF | Temperature unit | ℃=Celsius ℉=Fahrenheit | ℃ |