Features
Temperature display
Temperature control
Retain freshness defrost by turning off
comp.,freeze defrost type optional
Light control
High low temperature alarm/Self testing
Technical Data
Temperature display range:-45℃~120℃(-49~248℉)
Set temperature range:-30℃~20℃(-22~68℉)
Accuracy:±1℃(1℉)
Temperature sensor: NTC, two sensors, 2 meters (Neither positive nor negative ,white)
Retain freshness Compressor :NO. 10A/250VAC
Freeze compressor: NO. 30A/250VAC
Retain freshness Light :8A/250VAC
Freeze light: 8A/250VAC
Dimension:208(Length)×64(Width)×72.5(Depth)mm
Mounting hole dimension:192.5(Length)×58(Width)mm
Parameters
Paramete |
Function |
Set range |
Default |
E1 |
Lowest set point limit |
-30℃/-22℉~Set temp. |
-5℃/-23℉ |
E2 |
Higher set point limit |
Set temp.~20℃/68℉ |
12℃/54℉ |
E3 |
hysteresis |
01~20℃/02~36℉ |
05℃/09℉ |
E4 |
Comp.start delay time |
00~10Min |
2Min |
E5 |
Offset on room temp. |
-20~20℃/-36~36℉ |
00℃/00℉ |
F1 |
Max defrost duration |
01~60min |
20min |
F2 |
Defrost interval time |
00~24Hr |
0Hr |
F4 |
Display during defrost |
00=normal display 01=last value before defrost 02=DEF |
01 |
C1 |
Cold room high temperature alarm |
C2~120℃/248℉ |
80℃/176℉ |
C2 |
Cold room low temperature alarm |
-45℃/-49℉~C1 |
-25℃/-13℉ |
C3 |
Alarm hysteresis |
01~20℃/02~36℉ |
02℃/04℉ |
C4 |
Alarm delay |
00~60min |
-