Features
Temperature control
Temperature display
Automatic defrost contro
Exterior alarm
Technical Data
Temperature display range: -50℃~150℃(Resolution: 0.1℃)
Temperature set range: -45℃~145℃(set step:0.1℃, can limit set range)
Temperature sensor:NTC R25=10kΩ,B=3308K
Compressor:16A/250VAC
Defrosting output:5A/250VAC
Dimension:77(Length)×35(Width)×60(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
Parameters
Sort |
Code |
Parameter name |
Set range |
Factory default |
Remark |
Temperature control |
E1 |
Higher setpoint limit |
-45 ~145℃ |
145℃ |
- |
E2 |
Lower setpoint limit |
-45 ~145℃ |
-15℃ |
Control temperature setting, the parameter E2 must<E1. |
|
E3 |
Temp.hysteresis |
0.1 ~20℃ |
1.0℃ |
Hysteresis of control temperature, please refer to the theory about temperauter control. |
|
E4 |
Comp.Stop time for protection |
0 ~10Min |
3Min |
- |
|
E5 |
Water Temp.sensor offset |
-20.0 ~ 20.0℃ |
0.0℃ |
Offset on water temperature sensor. |
|
E6 |
Extraventricular system sensor offset |
-20.0 ~ 20.0℃ |
0.0℃ |
Offset on accuracy of extraventricular system sensor. |
|
Defrosting |
F1 |
Defrost.Start.Temp. |
-20 ~20℃ |
-20℃ |
The defrosting start temperature F1 must< the end temperature of defrosting F2. |
F2 |
Defrost.End.Temp. |
0 ~50℃ |
10℃ |
- |
|
F3 |
Defrost.Start time |
0 ~999Min |
30Min |
- |
|
F4 |
Max.defrost.Time |
0 ~99Min |
10Min |
0 means ther is no defrosting function. |
|
F5 |
Defrost.Mode |
0 ~3 |
0 |
0- four-way valve, it works when defrosting 1- four-way valve, it is off when defrosting 2- side-way valve 3- electric heater |
|
Alarm |
P1 |
Exterior alarm mode |
0~4 |
0 |
0- Do not use exterior alarm 1- N.O., unlock 2- N.O., lock 3- N.C., Unlock 4- N.C., Lock |
|
-