Features
Temperature Display
Automatic refrigerating and heating temperature control
Turning off, hot gas, heating defrost function
Pressure switch alarm/ High low temperature alarm
Fan Control/ Password control/ Parameter Locking/Self-testing
Technical Data
Range of temperature display:-45~120℃(-49~248℉)
Set temperature step value 0.1℃
Temperature sensor: NTC, 2 sensors, 2 meters long, neither positive nor negative.
Compressor: N.O. 16A/250VAC
Defrost: N.O. 8A/250VAC
Fan: N.O. 8A/250VAC
Heater: N.O. 8A/250VAC
Display Dimension:77(Length)×35(Width)×60(Depth)mm
Mounting hole dimension:71(Length)×29(Width)mm
Parameters
Parameter |
Function |
Set range |
Default |
E1 |
Lowest set temp. |
-40℉/-40℃~Set temp. |
41.0℉/5.0℃ |
E2 |
Highest set temp. |
Set temp.~248℉/120℃ |
140℉/60.0℃ |
E3 |
Heating Hysteresis |
0.2~18.0℉/0.1~10.0℃ |
3.6℉/2.0℃ |
E4 |
Refrigeration hysteresis |
0.2~18.0℉/0.1~10.0℃ |
3.6℉/2.0℃ |
E5 |
Delay starting time |
00~10Min |
2Min |
E6 |
Offset on room temp. |
-18.0~18.0℉/-10.0~10.0 ℃ |
0.0℉/0.0℃ |
E7 |
Offset on evap. Temp. |
-18.0~18.0℉/-10.0~10.0 ℃ |
0.0℉/0.0℃ |
E8 |
Fan delay time |
00~10Min |
3Min |
F0 |
defrost type |
00=电热化霜 01=热气化霜 |
00 |
F1 |
defrost duration |
00~60Min |
20Min |
F2 |
defrost interval |
00~24Hr |
4Hr |
F3 |
Defrost termination temp. |
-31~140℉/-35~60.0℃ |
46.4℉/8.0℃ |
F4 |
Display during defrost |
00=Normal display 01 = Last value before defrost 02= display dEF |
00 |
F6 |
Defrost dripping time |
00~60Min |
3Min |
C1 |
Temperature unit |
00=℃ 01= ℉ |
00 |
C2 |
High temp. alarm value |
C3~248℉/120℃ |
113℉/45.0℃ |
C3 |
Low temp. alarm value |
-49℉/-45℃~C2 |
5.0℉/-15.0℃ |
C4 |
Alarm hysteresis |
0.2~18.0℉/0.1~10.0℃ |
3.6℉/2.0℃ |
C5 |
Alarm delay time |
00~90Min |
5Min |
C6 |
heating cooling switch time |
00~60Min |
2Min |
L1 |
Failure working time |
01~120 Min |
30Min |
L2 |
Failure stop time |
01~120 Min |
15Min |
L3 |
Password setting |
000= no pass word other password |
000 |
-