SF-548N temperature humidity wine cabinet controller


Product number:1033013990369615872

  • Description
  • "

    Features 
    Mini-sized and integrated intelligent control.
    Temperature display/Temperature control/Automatic heating and cooling control/
    Humidity display /Humidity control/ Manual, automatic defrost/
    Light control/Evap. Fan control/Parameter looking/
    Value storing/Self testing

    Technical Data 
    Temperature sensor: two sensors, NTC,3m(L), neither  positive nor negative (Accuracy:±1%)
    Humidity sensor: one, 3m(L)  (Accuracy:±5%)
    Range of temperature display: -45~120℃(-49~248℉)
    Resolution: 01℃(02℉)
    Range of set temperature : 15~25℃(59~77℉)
    Factory default:15℃(59℉)
    Range of humidity display:00~100%RH
    Range of set humidity:55~75%RH
    Display panel dimension:208mm(Length) ×64mm(Width)×40mm(Depth)
    Mounting hole dimension: 192.5mm(Length) × 58mm(Width)
    Main frame dimension:150mm(Length)×130mm(Width)×55mm(Depth)
    Temperature of the operating environment:-10~60℃(14~140℉)
    Relative Humidity:20%~90%(Non-condensing)
    Relay output contact capacity:
    Compressor: N.O.30A/250VAC
    Heater:
    N.O.12A/250VAC
    Evap. Fan: N.O.10A/250VAC
    Humidifier:  N.O.10A/250VAC
    Light: N.O.10A/250VAC

    Paramete

    Paramete Function Set range Default
    PA Password 00~50~99 00
    E1 Lower set point limit
    -35℃
    -31℉  ~set temp.
    15℃
    59℉
    E2 Higher set point limit
    ~set temp.~  50℃
    122℉
    25℃
    77℉
    E3 Refrigeration hysteresis
    01~20℃
    02~36℉
    25℃
    77℉
    E4 Heating hysteresis
    01~20℃
    02~36℉
    02℃
    04℉
    E5 Refrigeration delay start 00~10min 03 min
    E6 Heating  delay start 00~10 min 01 min
    E7 Offset on room temp.
    -20~20℃
    -36~36℉
    00℃
    00℉
    E8 Offset on evap. Temp.
    -20~20℃
    -36~36℉
    00℃
    00℉
    E9 Offset on humidity -20~20% 00%
    F1 Max. Defrost duration 01~60 min 20 min
    F2 Defrost start temp
    -10~20℃
    14~68℉
    -1℃
    30℉
    F3 Defrost interval time 00~24hr 2hr
    F4 Displaying during defrost
    00=Normal display
    01=Last value
    before defrost
    01
    F5 Defrost termination temp.
    0~20℃
    32~68℉
    8℃
    46℉
    CF Temperature unit ℃=Celsius ℉=Fahrenheit
    D1 Fan delay stop 00~60 min 1 min
    D2 Fan control
    00=synchronized with heating, humidify,
    and the compressor, stop when defrost
    01=synchronized with heating, humidify,
    and the compressor, start when defrost
    02= keep working, start when defrost
    03= keep working, stop when defrost
    01
    D3 Alarm delay time 00~60min 2 min
    HA High temp. Alarm
    Lo~50℃
    122℉
    40℃
    104℉
    LO Low temp. Alarm
    -30℃
    -22℉~HA
    08℃
    46℉
    A0 Humidity control
    00=invalid(display only)
    01=valid
    01
    A1 Lowest humidity display 00~50% 45%
    A2 Highest humidity display 50~99% 85%
    A3 Lowest set humidity 00%~set humidity 55%
    A4 Highest set humidity set humidity~95% 75%
    A5 Humidify hysteresis 01~30% 05%
    A6 Humidify delay start time 00~120s 60s
    B1 Dehumidify hysteresis
    01~20℃
    02~36℉
    02℃
    04℉
    B2 Dehumidify time 01~90min 50 min
    T1 Force dehumidify interval 05~90 min 50 min
    T2 Force dehumidify time 01~90 min 10 min
    P0 Light duration
    00~120min
    (00 is infinite long)
    00 min
    P1 Sterilization cycle
    00~24hr
    (00, cancel the sterilization)
    00hr
    P2 Sterilization time 01~90 min 20 min
    LE Back light mode control
    00=energy saving
    01=energy consumption
    00
    CE Display language Cn= Chinese  En=English Cn
    CPA
    Change menu
    password
    00~ 99
    (if set 00, means cancel locking)